California Fire Protection and Backflow Compliance Calendar

The recurring inspection and testing duties that sit on the owner of a commercial or apartment building in California, and on the manager who tracks them for the owner. Every item on this page names the rule it comes from, and the sources are listed at the bottom.

Local fire departments and water purveyors can require more than the state floor. Treat this calendar as the starting point for each building, and confirm the local list with the fire department and the water purveyor for that address.

Download the free one-page PDF

The PDF is the same calendar on one page, sized for an owner or tenant packet. We recheck the sources on this page every quarter. Last checked November 23, 2026.

Every month

Monthly duties.
ItemWhat happensWho does it
Fire extinguishers, visual checkEach extinguisher is looked over at least monthly: in its place, charged, pin and seal in place, no visible damage.The building owner, occupant, or their agent
Emergency lights, short testThe battery test runs for at least 30 seconds. Exit sign lighting is checked at intervals of no more than 30 days.Building staff

Sources: Title 19, California Code of Regulations, sections 574.1 and 575.1 (extinguishers); NFPA 101, section 7.9.3, as described by NFPA (emergency lighting).

Every six months

Semiannual duties.
ItemWhat happensWho does it
Kitchen hood suppression systemThe fixed extinguishing system over commercial cooking equipment is serviced at least every six months, and again right after any time the system fires. A certificate of inspection goes to the fire code official.A qualified service company

Sources: Title 19, section 904(a)(2); California Fire Code, section 904.13.5.2.

Every year

Annual duties.
ItemWhat happensWho does it
Backflow prevention assembliesEach assembly is field tested at least once a year, and again after installation, repair, or relocation. The water purveyor sets the due date, takes the test report, and can shut off water when a test is missed.A certified backflow tester hired by the property
Fire extinguishers, maintenanceEvery extinguisher gets full maintenance once a year, beyond the monthly visual check.A company holding a State Fire Marshal extinguisher concern license
Emergency lights, full testThe battery test runs for the full 90 minutes once a year.Building staff or a service company
Fire alarm systemsInspection and testing follow the NFPA 72 schedule that the California Fire Code points to. Most components are tested at least once a year. Smoke detector sensitivity is checked within one year of installation and every second year after that.A fire alarm service company
Fire and smoke doorsDoor assemblies are inspected once a year and the inspection is documented for the fire department.The building owner's service provider
Hood system fusible linksFusible links on the kitchen hood system are replaced at least once a year.The hood service company
Private fire hydrants and fire mainsWhere the local fire department requires them, an annual inspection report for the property's private fire main and hydrants, which belong to the property owner.A fire protection company

Sources: Cross-Connection Control Policy Handbook, sections 3.3.3 and 3.4.1 (backflow); Title 19, section 575.1 (extinguishers); NFPA 101 (emergency lighting); California Fire Code, sections 901.6.1, 904.13.5.3, 507.5.2 and 901.6, with NFPA 72 and NFPA 80 (alarms, doors, hydrants).

Sprinklers run on the NFPA 25 schedule

California does not print its own sprinkler calendar. Title 19, section 904(a)(1) adopts NFPA 25, and the work follows the frequencies that standard sets for sprinkler systems, standpipes, and fire department connections.

The work is done by a CSLB C-16 Fire Protection contractor or by a company holding a State Fire Marshal AES license. California law names both routes, in Health and Safety Code section 13195.5.

Sources: Title 19, section 904; Contractors State License Board, C-16 Fire Protection classification; State Fire Marshal, Automatic Fire Extinguishing Systems program.

Five years and longer

Long-cycle duties.
ItemWhat happensWho does it
Private fire mainsA five year inspection report where the local fire department requires one, next to the annual report.A fire protection company
Stored pressure dry chemical extinguishersUnits on a 12 year hydrostatic cycle are emptied and given internal maintenance every six years. Hydrostatic testing itself runs every five years or every 12 years, depending on the extinguisher type.An OSFM licensed extinguisher company

Sources: Title 19, section 904 and section 575.1; Title 8, section 6151, Table L-1 (hydrostatic intervals by type).

When things change

Some duties attach to an event rather than a date.

  • A new tenancy starts. Smoke alarms must be working when a new tenancy is created. The owner is responsible for testing and maintaining them, and for fixing any alarm a tenant reports as not working. State law sets no fixed test interval for this; the duty attaches to the turnover and to tenant reports. Carbon monoxide devices are required in units with a fuel burning heater or appliance, a fireplace, or an attached garage. Sources: Health and Safety Code sections 13113.7 and 17926.
  • A backflow assembly is installed, repaired, or moved. It is field tested again, on top of the annual test. Source: Cross-Connection Control Policy Handbook, section 3.3.3.
  • A kitchen hood system fires. It is serviced again right away, on top of the six month service. Source: Title 19, section 904(a)(2).

Backflow testing in the five counties

The annual test is state law. The details a manager works with, the due date, the report form, and the tester list, come from the water purveyor at each address. Since July 1, 2026, a tester must hold a certification from a State Water Board recognized organization: ABPA, ASSE 5110, or CA-NV AWWA. Some county programs still certify testers for assemblies inside buildings, so check which credential your purveyor accepts for the assembly at the meter.

  • Los Angeles County. LADWP and the Los Angeles County Waterworks Districts both run annual testing programs. The customer hires a certified tester and files the report, and service can be disconnected when a required assembly is not tested. Los Angeles County Public Health certifies testers for assemblies inside buildings.
  • Orange County. Irvine Ranch Water District and Anaheim Public Utilities each require a test every year, done by a certified tester on the purveyor's approved list.
  • San Diego County. The City of San Diego requires testing every year at the same time of year, by a tester on the city approved list, which takes AWWA CA-NV or ABPA certification plus a city orientation. Helix Water District and Otay Water District run the same annual cycle in their areas.
  • Riverside County. Western Water and Riverside Public Utilities require annual testing at the customer's expense. Riverside County registers testers who hold a recognized certification.
  • San Bernardino County. The San Bernardino Municipal Water Department and West Valley Water District require annual testing. Fontana Water Company requires an annual test and maintenance report after its first test of a device.

Sources: the Cross-Connection Control Policy Handbook and the State Water Board list of recognized tester certifications; LADWP and Los Angeles County Waterworks Districts backflow pages; Irvine Ranch Water District and Anaheim Public Utilities cross-connection pages; City of San Diego, Helix Water District, and Otay Water District backflow pages; Western Water and Riverside Public Utilities pages; San Bernardino Municipal Water Department Rule 22, West Valley Water District, and Fontana Water Company pages.

Find a licensed company

The fire protection work on this calendar belongs to licensed companies. Licensed to Protect lists the CSLB C-16 companies in each of the five counties, with each company's license status and expiry date read from the state list. We are a directory. We do not inspect, test, or service anything ourselves.